MRC | Criteria | Characteristic |
---|
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 4 TOGGLE |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |
CPRX | ACTUATOR POSITION DESIGNATION | AT EACH POLE |
CPRY | EXTERNAL ACTUATOR LINKAGE ARRANGEMENT | ONE, TWO, THREE, AND FOUR LINKED |
CPRZ | AUXILIARY SWITCH FUNCTION AND QUANTITY | 1 ALARM |
CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP FIRST LOCATIONSERIES TRIP SECOND LOCATIONSERIES TRIP THIRD LOCATIONRELAY TRIP FOURTH LOCATION |
CQJX | NOMINAL THREAD SIZE | 0.138 INCHES |
CQSM | SWITCH LOCATION AND POSITION DESIGNATION | INTERNAL AT POLE THREE |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 0.600 MINIMUM AT 200 PCT FIRST LOCATION AND 5.000 MAXIMUM AT 200 PCT FIRST LOCATION0.600 MINIMUM AT 200 PCT SECOND LOCATION AND 5.000 MAXIMUM AT 200 PCT SECOND LOCATION0.600 MINIMUM AT 200 PCT THIRD LOCATION AND 5.000 MAXIMUM AT 200 PCT THI |
CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | EXPLOSION PROOF AND FUNGUS RESISTANT AND MOISTURE RESISTANT AND SHOCK RESISTANT AND |
CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | VIBRATION RESISTANT |
CRTK | SWITCH TERMINAL TYPE | TAB, SOLDER LUG |
CSSX | SWITCH CURRENT RATING AND TYPE IN AMPS | 5.0 AC AND 1.0 DC |
CSWP | SWITCH VOLTAGE RATING AND TYPE IN VOLTS | 125.0 AC AND |
CSWP | SWITCH VOLTAGE RATING AND TYPE IN VOLTS | 50.0 DC |
FREQ | FREQUENCY IN HERTZ | 400.0 ALL LOCATIONS |
THSD | THREAD SERIES DESIGNATOR | UNC |
TTQY | TERMINAL TYPE AND QUANTITY | 10 THREADED STUD |
ZZZK | SPECIFICATION/STANDARD DATA | 12436-A15912 GOVERNMENT SPECIFICATION |
AAQL | BODY STYLE | MULTIPOLE-MULTIPLE ACTUATOR TYPE |
ADAQ | BODY LENGTH | 2.530 INCHES MAXIMUM |
ADAT | BODY WIDTH | 3.060 INCHES MAXIMUM |
ADTV | CASE MATERIAL | PLASTIC |
AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 1.940 INCHES MAXIMUM |
AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 0.750 INCHES MINIMUM AND 0.770 INCHES MAXIMUM |
AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 2.050 INCHES MINIMUM AND 2.070 INCHES MAXIMUM |
AEGJ | SWITCH CONTACT ARRANGEMENT | SINGLE POLE, DOUBLE THROW |
AEHA | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 0.750 INCHES MINIMUM AND 0.770 INCHES MAXIMUM |
AFJN | III FRAGILITY FACTOR | MODERATELY RUGGED |
AJEC | BOSS HEIGHT | 0.150 INCHES MAXIMUM |
AJWX | MOUNTING SURFACE TO TERMINAL END DISTANCE | 2.522 INCHES MAXIMUM |
AKPX | POLE QUANTITY | 4 |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 8 THREADED HOLE |
BBRG | III STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
BBRJ | III SPECIAL HANDLING FEATURE | MAGNETIC |
CMLP | THREAD QUANTITY PER INCH | 32 |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 30.0 AMPERES AC ALL LOCATIONS |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 250.0 AC ALL LOCATIONS |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 1500.0 AC ALL LOCATIONS |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
CPRJ | TRIP RELEASE METHOD | MAGNETIC-HYDRAULIC ALL LOCATIONS |
CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY FIRST LOCATIONTIME DELAY SECOND LOCATIONTIME DELAY THIRD LOCATIONINSTANTANEOUS FOURTH LOCATION |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 150.0 ALL LOCATIONS |
CPRQ | RESET METHOD | MANUAL |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |